Sizing the Array
![]() Independent of the system design type, the first step in sizing any solar array is to determine what the hot water load is. Knowing the BTU/day requirements of the load, the solar array can then be sized to meet it. The table below gives the average daily draws in GPD (gallons per day) for a wide variety of commercial applications. These average daily draws are based on ASHRAE guidelines and contractor experience.
|
||||||||||||||||||||||||||||||||||
| Converting the Hot Water Draw to BTU's | ||||||||||||||||||||||||||||||||||
|
In order to use the daily draw calculated from the table above, we must
convert it from gallons per day to BTU's per day. This conversion
relies on the fact that it takes 8.34 BTU's (British Thermal Units) of
energy to raise 1 gallon of water 1 degree F. If solar is to be
used as a pre-heater for the existing boiler loop, which is typical, then it
will have to raise each gallon of water drawn from mains/wellwater temperature up to
the typical desired setpoint of 135 F. Depending on the region of the
country, average mains/wellwater temperatures may be as low as 42°F in
northern Maine up to 77°F in southern Florida. To determine the energy
required to heat each gallon of water, we simply calculate the temperature
difference between the mains/wellwater and the setpoint temperature and then
multiply that difference by 8.34. Therefore, it would take 776 BTU (8.34 BTU/gal-F*[135 F -
42 F]) on average to heat a gallon of water in northern Maine and only 484
BTU (8.34 BTU/gal-F*[135 F - 77 F]) in southern Florida. |
||||||||||||||||||||||||||||||||||
| Calculating the Collector Area Required to Meet Hot Water Demands | ||||||||||||||||||||||||||||||||||
|
Optimal sizing of
the solar array is achieved by matching the load to the output
of the solar array on a clear summer day. By matching system output
to clear summer days you ensure that the system functions at maximum
capacity without going into stagnation conditions that can decrease
component life. Sizing systems along these lines typically results
in solar fractions of 60-70%. Rsizing=1.15*8.34*(135-Tmains/well)/Qcollector Where
Qcollector is the collector output of either 984 or 1040
BTU/sq. ft. The factor of 1.15 at the start of the equation is to
oversize the array by 15% to account for real world losses in the piping
runs and storage tank as well as mild flow non-uniformities that occur
between banks in commercial arrays. Using this equation we would
come up with a sizing ratio of 0.56 sq. ft./GPD draw for a system in
southern Florida using painted absorbers, and a ratio of 0.86 sq. ft./GPD
draw for a system in northern Maine with chrome absorbers. |


